Skip to content

Max Zs for 125A Type C MCB

BS 7671 Table 41.3 — BS 7671:2018+A2:2022

Max Zs (0.4s)

0.17Ω

Testing Limit

0.14Ω

Max Zs (5s)

0.35Ω

Ia (0.4s)

1250A

At a Glance

Device
MCB Type C125A
Standard
BS EN 60898
Max Zs (0.4s)
0.17Ω
Max Zs (5s)
0.35Ω
Testing Limit (80%)
0.14Ω
Ia (0.4s)
1250A

About MCB Type C

Type C MCBs trip magnetically at 5–10× In. They are designed for circuits with moderate inrush current — motor-driven equipment, air conditioning, and discharge lighting. The higher trip multiplier means lower maximum Zs values, so circuit impedance must be kept tighter than with Type B devices.

Worked Example: Maximum Cable Run for 125A MCB Type C

  1. Maximum Zs (tabulated) = 0.17Ω (BS 7671 Table 41.3)
  2. Testing limit (80%) = 0.17 × 0.8 = 0.14Ω
  3. Assume Ze = 0.8Ω (typical TN-S supply)
  4. Maximum R1+R2 = 0.14 − 0.8 = —Ω
  5. Using 25mm² T&E: R1+R2 = 1.47 mΩ/m
  6. The available R1+R2 margin is insufficient for standard cable — verify the earthing arrangement.

The tight Zs limit for this device means cable runs must be very short. Verify the supply earthing type and consider whether a lower-rated or different device type is more appropriate.

0.4s vs 5s Disconnection — Different Values for Type C

Type C MCBs require 10× In for 0.4s disconnection but only 5× In for 5s. At 125A: max Zs = 0.17Ω (0.4s) vs 0.35Ω (5s). For distribution circuits (5s allowed), you have nearly double the impedance budget. Final circuits serving socket outlets must still meet the 0.4s limit.

Disconnection TimeMax ZsTesting Limit (80%)
0.4 seconds0.17Ω0.14Ω
5 seconds0.35Ω0.28Ω

125A Across Device Types

Device TypeMax Zs (0.4s)Testing Limit
MCB Type B0.35Ω0.28Ω
MCB Type C0.17Ω0.14Ω
MCB Type D0.09Ω0.07Ω
BS 88 Fuse0.27Ω0.22Ω

Frequently Asked Questions

Built by Taro Schenker · Need a website for your trade business? Get in touch