Max Zs for 100A Type D MCB
BS 7671 Table 41.3 — BS 7671:2018+A2:2022
Max Zs (0.4s)
0.11Ω
Testing Limit
0.09Ω
Max Zs (5s)
0.11Ω
Ia (0.4s)
2000A
At a Glance
- Device
- MCB Type D — 100A
- Standard
- BS EN 60898
- Max Zs (0.4s)
- 0.11Ω
- Max Zs (5s)
- 0.11Ω
- Testing Limit (80%)
- 0.09Ω
- Ia (0.4s)
- 2000A
About MCB Type D
Type D MCBs trip magnetically at 10–20× In. They handle the highest inrush currents — transformers, welding equipment, and X-ray machines. The very high trip multiplier produces very low max Zs values, which severely limits cable run lengths. Type D devices are rarely suitable for final circuits with 0.4s disconnection requirements.
Worked Example: Maximum Cable Run for 100A MCB Type D
- Maximum Zs (tabulated) = 0.11Ω (BS 7671 Table 41.3)
- Testing limit (80%) = 0.11 × 0.8 = 0.09Ω
- Assume Ze = 0.8Ω (typical TN-S supply)
- Maximum R1+R2 = 0.09 − 0.8 = —Ω
- Using 25mm² T&E: R1+R2 = 1.47 mΩ/m
- The available R1+R2 margin is insufficient for standard cable — verify the earthing arrangement.
The tight Zs limit for this device means cable runs must be very short. Verify the supply earthing type and consider whether a lower-rated or different device type is more appropriate.
0.4s vs 5s Disconnection — Significant Difference for Type D
At 100A, the max Zs values for Type D are 0.11Ω for both disconnection times.
100A Across Device Types
| Device Type | Max Zs (0.4s) | Testing Limit |
|---|---|---|
| MCB Type B | 0.44Ω | 0.35Ω |
| MCB Type C | 0.22Ω | 0.18Ω |
| MCB Type D | 0.11Ω | 0.09Ω |
| BS 88 Fuse | 0.21Ω | 0.17Ω |