Max Zs for 100A Type D MCB

BS 7671 Table 41.3 — BS 7671:2018+A2:2022

Max Zs (0.4s)

0.11Ω

Testing Limit

0.09Ω

Max Zs (5s)

0.11Ω

Ia (0.4s)

2000A

At a Glance

Device
MCB Type D100A
Standard
BS EN 60898
Max Zs (0.4s)
0.11Ω
Max Zs (5s)
0.11Ω
Testing Limit (80%)
0.09Ω
Ia (0.4s)
2000A

About MCB Type D

Type D MCBs trip magnetically at 10–20× In. They handle the highest inrush currents — transformers, welding equipment, and X-ray machines. The very high trip multiplier produces very low max Zs values, which severely limits cable run lengths. Type D devices are rarely suitable for final circuits with 0.4s disconnection requirements.

Worked Example: Maximum Cable Run for 100A MCB Type D

  1. Maximum Zs (tabulated) = 0.11Ω (BS 7671 Table 41.3)
  2. Testing limit (80%) = 0.11 × 0.8 = 0.09Ω
  3. Assume Ze = 0.8Ω (typical TN-S supply)
  4. Maximum R1+R2 = 0.09 − 0.8 = —Ω
  5. Using 25mm² T&E: R1+R2 = 1.47 mΩ/m
  6. The available R1+R2 margin is insufficient for standard cable — verify the earthing arrangement.

The tight Zs limit for this device means cable runs must be very short. Verify the supply earthing type and consider whether a lower-rated or different device type is more appropriate.

0.4s vs 5s Disconnection — Significant Difference for Type D

At 100A, the max Zs values for Type D are 0.11Ω for both disconnection times.

100A Across Device Types

Device TypeMax Zs (0.4s)Testing Limit
MCB Type B0.44Ω0.35Ω
MCB Type C0.22Ω0.18Ω
MCB Type D0.11Ω0.09Ω
BS 88 Fuse0.21Ω0.17Ω