Bathroom Electrical Zones Guide
Complete guide to bathroom electrical zones 0, 1, and 2 under BS 7671 Section 701, including IP ratings, equipment selection, and installation requirements.
What Are Bathroom Electrical Zones?
BS 7671 Section 701 divides bathrooms and shower rooms into defined zones that determine what electrical equipment can be installed and the IP ratings required. Understanding these zones is essential for any electrical work in a bathroom.
Bathroom zone definitions
BS 7671 Regulation 701.32| Zone | Boundary Definition | Height |
|---|---|---|
| Zone 0 | Interior of the bath tub or shower tray | Up to the top of the bath rim or shower tray |
| Zone 1 | Directly above Zone 0 | From Zone 0 up to 2.25m from the finished floor level |
| Zone 2 | 0.6m horizontally beyond Zone 1 | Up to 2.25m from the finished floor level |
| Outside zones | Beyond Zone 2 in all directions | Above 2.25m everywhere, and beyond 0.6m from Zone 1 |
Where there is no bath tray or shower tray, Zone 0 is the floor area beneath the shower head to a depth of 0.05m and Zone 1 extends 1.2m from the water outlet.
Shower Without a Tray
What IP Ratings Are Required in Each Zone?
IP (Ingress Protection) ratings define how well equipment resists water ingress. Each bathroom zone has minimum IP rating requirements to prevent electric shock.
Minimum IP ratings by bathroom zone
BS 7671 Section 701 and BS EN 60529| Zone | Minimum IP Rating | Protection Level | Notes |
|---|---|---|---|
| Zone 0 | IPX7 | Protection against temporary immersion | Equipment must withstand submersion to 1m for 30 minutes |
| Zone 1 | IPX4 | Protection against splashing from any direction | IPX5 required where water jets are used for cleaning (e.g., communal showers) |
| Zone 2 | IPX4 | Protection against splashing from any direction | Same as Zone 1 for splash resistance |
| Outside zones | General | No specific minimum for water ingress | Consider splash risk — IPX4 recommended in humid bathrooms |
IP ratings comprise two digits: the first for solid object protection, the second (after 'X') for water protection.
IPX5 for Communal Areas
What Electrical Equipment Can I Install in Each Zone?
Each zone restricts the type of electrical equipment that can be installed. The closer to the water source, the more restrictive the requirements.
Permitted equipment by zone
BS 7671 Regulation 701.55 and 701.512.3| Zone | Permitted Equipment | Voltage / Supply | Key Restrictions |
|---|---|---|---|
| Zone 0 | Fixed SELV equipment only (e.g., chromotherapy lights) | 12V AC / 30V DC SELV maximum | Safety isolating transformer must be outside Zones 0, 1, and 2 |
| Zone 1 | SELV devices, fixed water heaters, electric showers, shower pumps (IPX4+) | SELV or 230V for fixed current-using equipment | No switchgear except SELV switches; no socket outlets |
| Zone 2 | All Zone 1 items plus luminaires, fans, shaver sockets (BS EN 61558-2-5), heated towel rails | 230V with 30mA RCD protection | Shaver sockets must have isolating transformer |
| Outside zones | Most equipment permitted with appropriate IP rating | 230V with 30mA RCD protection | Standard 13A sockets must be 3m+ from Zone 1 |
Electric Shower Installation
Do Bathrooms Need RCD Protection?
RCD protection is mandatory for all circuits serving a bathroom or shower room, regardless of which zone the equipment is installed in.
Regulation 701.411.3.3 requires that every circuit serving a location containing a bath or shower is protected by a 30mA RCD. This applies to all circuits — lighting, power, heating, and ventilation — not just those with accessories within the zones. There are no exceptions for fixed equipment.
RCD protection requirements for bathrooms
BS 7671 Regulation 701.411.3.3| Circuit Type | RCD Required | Rating | Notes |
|---|---|---|---|
| Lighting | Yes | 30mA | Including circuits outside zones |
| Electric shower | Yes | 30mA | Dedicated circuit required |
| Heated towel rail | Yes | 30mA | Fused connection unit or RCBO |
| Extractor fan | Yes | 30mA | Often on lighting circuit |
| Shaver socket | Yes | 30mA | Isolating transformer provides additional protection |
| Underfloor heating | Yes | 30mA | Electric UFH in bathroom zones |
Circuits that merely pass through the bathroom (e.g., to another room) also require 30mA RCD protection.
No Exceptions
Is Supplementary Bonding Still Required in Bathrooms?
Amendment 2 of BS 7671 introduced conditions under which supplementary bonding in bathrooms can be omitted, but the requirements must be carefully verified.
Under Regulation 701.415.2, supplementary bonding within a bathroom can be omitted where all of the following conditions are satisfied:
Conditions for omitting supplementary bonding
BS 7671 Regulation 701.415.2| Condition | Requirement | How to Verify |
|---|---|---|
| RCD protection | All circuits in the bathroom have 30mA RCD protection | Check consumer unit — all bathroom circuits on RCD/RCBO |
| Disconnection times | Automatic disconnection times per Regulation 411.3.2 are met | Verify Zs values are within limits for all circuits |
| Main bonding | All extraneous-conductive-parts are connected to main protective bonding | Confirm bonding to gas, water, and any other metallic services |
When in Doubt, Bond
What Are the Key BS 7671 Regulations for Bathrooms?
A quick reference to the most important regulation numbers you need when designing or inspecting bathroom electrical installations.
Key BS 7671 bathroom regulations
BS 7671:2018+A2:2022 Section 701| Regulation | Subject | Summary |
|---|---|---|
| 701.1 | Scope | Applies to all rooms containing a bath or shower, including shower rooms without a bath |
| 701.32 | Classification of zones | Defines Zones 0, 1, and 2 boundaries and dimensions |
| 701.411.3.3 | RCD protection | 30mA RCD required for all circuits serving the bathroom location |
| 701.415.2 | Supplementary bonding | Conditions under which supplementary bonding may be omitted |
| 701.512.3 | Wiring systems | Cable installation requirements within zones — routing and concealment |
| 701.55 | Other equipment | Restrictions on switchgear, socket outlets, and accessories by zone |
Always refer to the full regulation text. This table provides a summary for quick reference only.
EICR Inspections — Bathroom Checklist