Skip to content

Battery Storage (BESS) Calculator

Size a domestic battery storage system \u2014 capacity, electrical requirements, and financial payback

Reference Info & Formulas
Popular Battery Systems

Tesla Powerwall: 13.5kWh, 5kW continuous

GivEnergy: 5 / 8.2 / 13.5kWh modular

Sunsynk: 5.12kWh stackable

All require dedicated circuit from consumer unit

DNO Rules

≤3.68kW: G98 notification (simple form)

>3.68kW: G99 application (10+ weeks)

Always notify DNO regardless of battery size

Property & Consumption
Daily electricity usage
Solar PV Details
Your existing solar installation

Auto-calculated: kWp x 2.7 (UK average)

Tariff Rates
Current electricity rates
Battery System
Battery and inverter specification

Data: BS 7671:2018+A2:2022, G98/G99, MCS Standards

For guidance only. The responsibility for any electrical installation lies with the qualified person carrying out the work. Always verify calculations independently and apply professional judgement.

How This Calculator Works

The battery storage calculator sizes a domestic BESS based on your energy consumption, solar generation, and financial parameters.

The calculator determines how much energy can realistically be stored and shifted from low-value export (or cheap off-peak import) to high-value peak consumption. It then sizes the electrical circuit for the battery inverter, checks DNO notification requirements, and calculates the financial payback period.

Daily savings = Stored kWh x (Import rate - Export rate)
Stored kWh
= Energy shifted from export/off-peak to peak use
Import rate
= Cost of electricity from the grid (p/kWh)
Export rate
= Rate received for exported solar (SEG, p/kWh)

Payback = Installed cost / Annual savings

The usable battery capacity accounts for depth of discharge (typically 90% for lithium-ion) and round-trip efficiency (approximately 90%). The daily stored energy is limited by whichever is smaller: the usable capacity or the available surplus energy from solar export or off-peak import.

Quick Reference \u2014 Battery Inverter Circuit Sizing

Typical inverter AC circuit requirements

BS 7671 Table 4D5, G98/G99 thresholds
Inverter RatingCurrent (A)Cable SizeMCBDNO
3.6kW15.7A2.5mm² T&E20AG98
5kW21.7A4mm² T&E25AG99
6kW26.1A4mm² T&E32AG99
8kW34.8A6mm² T&E40AG99
10kW43.5A10mm² T&E50AG99

Cable sizes assume Method C (clipped direct), 30\u00B0C ambient, no grouping or insulation derating. DNO column assumes single-phase; threshold is 3.68kW per phase.

Practical Notes

G98 vs G99 \u2014 DNO Notification

Every battery storage installation requires DNO notification. If the inverter output is 3.68kW or less per phase, submit a G98 notification form within 28 days of commissioning. Above 3.68kW per phase, a G99 application must be submitted and approved BEFORE commissioning. G99 applications typically take 10-12 weeks. Plan installations accordingly to avoid delays.

Right-size the Battery

A battery that is too large for the available surplus energy will sit partially charged most days, extending payback unnecessarily. Match the battery capacity to the available daily surplus: for a 4kWp solar system exporting 50% of generation, a 5kWh battery captures most of the excess without wasted capacity.

High-Voltage Battery Safety

Some battery systems operate at 400V DC or higher. These systems present a serious shock risk during installation and fault conditions. Ensure the installer has specific training for high-voltage DC systems, use appropriate PPE, and install DC isolation devices accessible for emergency disconnection. Type B RCD may be required for high-voltage DC battery inverters.

Frequently Asked Questions

SparkyHub is a free resource built by Taro Schenker — I build websites for trade businesses too.

Related Calculators

Built by Taro Schenker · Need a website for your trade business? Get in touch