Solar PV Electrical Calculator
DC & AC cable sizing, string configuration, and protection for solar PV installations
Reference Info & Formulas
DC cables: Rated for 1.25 × Isc
DC VD: Aim for ≤3%
AC VD: Max 2.5%
String Voc: Must not exceed inverter max
Find Vmp, Imp, Voc, Isc on the panel data sheet (STC values)
Apply temperature correction to Voc for cold site temps
Data: BS 7671:2018+A2:2022 Section 712, IET Code of Practice for Solar PV
For guidance only. The responsibility for any electrical installation lies with the qualified person carrying out the work. Always verify calculations independently and apply professional judgement.
How This Calculator Works
Solar PV electrical design requires sizing both DC and AC circuits, with string voltage and current calculations governed by BS 7671 Section 712.
A PV array consists of panels wired in series (strings) and sometimes in parallel. Panels in series add their voltages — so a string of ten panels at 37V Vmp produces 370V DC at maximum power point. The calculator determines string voltage, verifies it falls within the inverter's operating window, and sizes cables for both the DC and AC sides of the installation.
V_string = N × Voc × (1 + (T_min - 25) × α)- N
- = Number of panels in series
- Voc
- = Open-circuit voltage per panel at STC (25°C)
- T_min
- = Minimum expected cell temperature (°C)
- α
- = Temperature coefficient of Voc (typically -0.3%/°C)
BS 7671 Section 712, IEC 62548
DC cables must be rated for at least 1.25 times the short-circuit current (Isc) of the string. This safety factor accounts for irradiance levels that can momentarily exceed the STC rating of 1000 W/m², particularly with cloud-edge enhancement effects.
I_cable ≥ 1.25 × Isc- I_cable
- = Minimum cable current rating required
- Isc
- = Short-circuit current of the string at STC
BS 7671 Regulation 712.433.1
Quick Reference — Common PV Panel Specifications
Typical electrical data for residential PV panels
Typical manufacturer datasheets — always use actual panel specs for design| Panel Rating | Vmp (V) | Voc (V) | Imp (A) | Isc (A) |
|---|---|---|---|---|
| 330W (60-cell) | 33.5 | 40.5 | 9.85 | 10.44 |
| 400W (108 half-cell) | 37.0 | 44.8 | 10.81 | 11.47 |
| 420W (108 half-cell) | 38.2 | 45.6 | 11.0 | 11.65 |
| 500W (132 half-cell) | 41.7 | 49.9 | 12.0 | 12.72 |
STC conditions: 1000 W/m² irradiance, 25°C cell temperature, AM 1.5 spectrum.
Quick Reference — DC Cable Sizing
H1Z2Z2-K solar cable current ratings
EN 50618, manufacturer datasheets| Cable Size (mm²) | Current Rating (A) | Typical Use |
|---|---|---|
| 4mm² | 40A | Single string up to ~12A Isc |
| 6mm² | 55A | Two parallel strings or long runs |
| 10mm² | 75A | Multiple strings in parallel or long DC runs |
Ratings shown are for free air installation. Apply derating for bunched cables, conduit, or high ambient temperatures.
Practical Notes
Cold Weather Increases String Voltage
Use the Inverter MPPT Range for String Design
AC Side Protection — Type B MCB
Frequently Asked Questions
SparkyHub is a free resource built by Taro Schenker — I build websites for trade businesses too.
Related Calculators
Battery Storage
Size a domestic battery storage system with payback and electrical requirements
DNO Checker
Check if your installation needs a G98 notification or G99 application
Cable Size
Calculate the correct cable size for any circuit
RCD Selector
Select the correct RCD type and sensitivity for any circuit