Skip to content

Outbuilding Electrical Supply

Supplying outbuildings, garages, and garden offices — cable selection, earthing, and RCD protection

SWA cableEarthingRCDSubmain

SWA Cable Selection

Steel Wire Armoured (SWA) cable is the standard choice for underground supply to detached outbuildings.

Common SWA cable sizes for outbuilding supplies

BS 7671 Table 4D4A, Column 7
Cable Size (mm²)Rating (A) Direct BuriedTypical Use
437Lighting-only shed or small load
647Garden office, workshop up to 10 kW
1064Workshop with power tools, large office
1685High-load workshop, hot tub supply
25110Large annex, multiple circuits

Ratings for 3-core SWA direct buried. Apply derating factors for grouping, soil thermal resistivity, and depth.

VD = (mV/A/m x Ib x L) / 1000
mV/A/m
= Millivolt drop per amp per metre (from BS 7671 Table 4D4B)
Ib
= Design current in amps
L
= Cable run length in metres

BS 7671 Appendix 4, Regulation 525.1

Earthing Arrangements

The earthing arrangement for a detached outbuilding is a critical design decision that affects safety.

Where the main building has a PME (TN-C-S) supply, BS 7671 Regulation 411.4.2 restricts extending the PME earth to a detached outbuilding because a broken PEN conductor could place the full neutral voltage on the outbuilding's metalwork. The preferred solution is a TT earthing arrangement with a local earth electrode (typically a 1.2 m copper-clad earth rod driven at the outbuilding).

PME Restrictions

If PME earthing is extended to the outbuilding, main protective bonding must be provided to all extraneous-conductive-parts. This is often impractical in a detached structure. A TT earth with 30 mA RCD protection is simpler and safer in most cases.

Earth Electrode Resistance

A TT earth electrode should achieve a resistance low enough that the RCD can operate within the required disconnection time. With a 30 mA RCD, an earth electrode resistance of up to 1667 ohms is theoretically acceptable (50V / 0.03A), but aim for under 200 ohms in practice for reliable operation.

Installation Requirements

Key requirements checklist

BS 7671 18th Edition
RequirementDetailReference
Isolation at originSwitch or isolator in main buildingReg 537.2
Cable burial depth500 mm (hard surface) or 600 mm (open ground)Reg 522.8.10
Cable route protectionCable tiles above, marker tape 150 mm higherBest practice
RCD protection30 mA RCD for sockets and outdoor circuitsReg 411.3.3
Local consumer unitSeparate CU in outbuilding with main switchReg 514.12
Part P notificationNotifiable as new circuit to detached buildingBuilding Regs Part P

Voltage Drop Considerations

Outbuilding supplies often involve cable runs of 20-50 m or more. BS 7671 permits a maximum voltage drop of 5% (11.5 V at 230 V). Limit the sub-main drop to 3% (6.9 V) to leave headroom for final circuits.

Total Voltage Drop

The total voltage drop includes both the sub-main and the final circuit within the outbuilding. Check both stages to ensure the combined drop stays within 5%.

Frequently Asked Questions

Related Calculators

Built by Taro Schenker · Need a website for your trade business? Get in touch