Skip to content

Transformer & Busbar Sizing Calculator

Size distribution transformers, calculate fault levels, and select busbars

Reference Info & Formulas
Sizing Rules

125% Rule: Transformer rated at least 125% of the maximum demand.

Fault Level: If = FLC / (Z% / 100). Protective devices must have adequate breaking capacity.

Busbars: Rated for continuous FLC with temperature derating applied.

Standard TX Sizes

50, 100, 160, 200, 250, 315, 400, 500, 630, 800, 1000, 1250, 1600, 2000, 2500 kVA

Per BS EN 50464-1

Load Details
Enter connected load and diversity
kVA
m

Data: BS EN 50464-1, IEC 60076 — transformer and busbar sizing

For guidance only. The responsibility for any electrical installation lies with the qualified person carrying out the work. Always verify calculations independently and apply professional judgement.

Transformer Fault Level Calculation

The prospective fault current at the secondary terminals depends on the transformer rating and percentage impedance.

If = FLC / (Z% / 100)
If
= Fault current in amps
FLC
= Full load current of the transformer
Z%
= Percentage impedance of the transformer

IEC 60076 / BS 7671 Regulation 434

This gives the maximum prospective short-circuit current assuming an infinite source (negligible supply impedance). In practice, the supply impedance reduces the actual fault current, but the transformer-limited value is used for protective device selection as a safe assumption.

Standard Transformer Ratings

Three-phase oil-filled distribution transformers

BS EN 50464-1
Rating (kVA)Typical Z%400V FLC (A)Approx. Fault (kA)
1004.01443.6
2504.53618.0
5005.072214.4
10005.0144328.9
16005.5230942.0
25006.0360860.1

FLC calculated at 400V three-phase. Actual fault current depends on supply impedance.

Busbar Selection Notes

Derating for Ambient Temperature

Busbar ratings are based on 35–40°C ambient. In enclosed switchgear or hot environments, apply derating factors. A busbar in a 50°C panel may only deliver 90% of its published rating. Always check manufacturer data.

Fault Withstand

Busbars must withstand the thermal and electromagnetic effects of fault current for the disconnection time of the upstream protective device. Check both the continuous rating and the short-time withstand rating (typically 1 second).

Frequently Asked Questions

SparkyHub is a free resource built by Taro Schenker — I build websites for trade businesses too.

Related Calculators

Built by Taro Schenker · Need a website for your trade business? Get in touch