Max Zs for 15A BS 1361 Fuse
BS 7671 Table 41.4 — BS 7671:2018+A2:2022
Max Zs (0.4s)
3.12Ω
Testing Limit
2.5Ω
Max Zs (5s)
6.2Ω
Ia (0.4s)
70A
At a Glance
- Device
- BS 1361 Fuse — 15A
- Standard
- BS 1361
- Max Zs (0.4s)
- 3.12Ω
- Max Zs (5s)
- 6.2Ω
- Testing Limit (80%)
- 2.5Ω
- Ia (0.4s)
- 70A
About BS 1361 Fuse
BS 1361 cartridge fuses were commonly used in domestic consumer units before MCBs became standard. They are still found in older installations and are acceptable for continued use. Their max Zs values are generally more generous than equivalent MCB ratings.
Typical Circuits for 15A BS 1361 Fuse
| Circuit | Cable Size | Notes |
|---|---|---|
| Immersion heater | 2.5mm² | Dedicated water heating circuit |
Worked Example: Maximum Cable Run for 15A BS 1361 Fuse
- Maximum Zs (tabulated) = 3.12Ω (BS 7671 Table 41.4)
- Testing limit (80%) = 3.12 × 0.8 = 2.5Ω
- Assume Ze = 0.35Ω (typical TN-C-S (PME) supply)
- Maximum R1+R2 = 2.5 − 0.35 = 2.15Ω
- Using 1.5mm² T&E: R1+R2 = 24.2 mΩ/m
- Maximum cable run = 2.15 ÷ 0.0242 = 88.8m
On a TN-C-S (PME) supply with 1.5mm² cable, the maximum one-way cable run is approximately 88.8m before Zs exceeds the testing limit. In practice, always measure — parallel earth paths and cable route conditions will affect the actual value.
0.4s vs 5s Disconnection Times
Fuse characteristics differ from MCBs — disconnection time depends on the time/current curve. At 15A: max Zs = 3.12Ω (0.4s) vs 6.2Ω (5s). The 5s value is higher because a lower fault current will still melt the fuse element given more time. Use the 0.4s value for final circuits and 5s for distribution circuits only.
| Disconnection Time | Max Zs | Testing Limit (80%) |
|---|---|---|
| 0.4 seconds | 3.12Ω | 2.5Ω |
| 5 seconds | 6.2Ω | 4.96Ω |
15A Across Device Types
| Device Type | Max Zs (0.4s) | Testing Limit |
|---|---|---|
| BS 1361 Fuse | 3.12Ω | 2.5Ω |
| BS 3036 Semi-enclosed Fuse | 2.76Ω | 2.21Ω |