Max Zs for 30A BS 1361 Fuse
BS 7671 Table 41.4 — BS 7671:2018+A2:2022
Max Zs (0.4s)
1.61Ω
Testing Limit
1.29Ω
Max Zs (5s)
3.2Ω
Ia (0.4s)
136A
At a Glance
- Device
- BS 1361 Fuse — 30A
- Standard
- BS 1361
- Max Zs (0.4s)
- 1.61Ω
- Max Zs (5s)
- 3.2Ω
- Testing Limit (80%)
- 1.29Ω
- Ia (0.4s)
- 136A
About BS 1361 Fuse
BS 1361 cartridge fuses were commonly used in domestic consumer units before MCBs became standard. They are still found in older installations and are acceptable for continued use. Their max Zs values are generally more generous than equivalent MCB ratings.
Typical Circuits for 30A BS 1361 Fuse
| Circuit | Cable Size | Notes |
|---|---|---|
| Ring final / cooker | 2.5–6.0mm² | Older consumer unit configuration |
Worked Example: Maximum Cable Run for 30A BS 1361 Fuse
- Maximum Zs (tabulated) = 1.61Ω (BS 7671 Table 41.4)
- Testing limit (80%) = 1.61 × 0.8 = 1.29Ω
- Assume Ze = 0.35Ω (typical TN-C-S (PME) supply)
- Maximum R1+R2 = 1.29 − 0.35 = 0.94Ω
- Using 4mm² T&E: R1+R2 = 9.22 mΩ/m
- Maximum cable run = 0.94 ÷ 0.00922 = 102m
On a TN-C-S (PME) supply with 4mm² cable, the maximum one-way cable run is approximately 102m before Zs exceeds the testing limit. In practice, always measure — parallel earth paths and cable route conditions will affect the actual value.
0.4s vs 5s Disconnection Times
Fuse characteristics differ from MCBs — disconnection time depends on the time/current curve. At 30A: max Zs = 1.61Ω (0.4s) vs 3.2Ω (5s). The 5s value is higher because a lower fault current will still melt the fuse element given more time. Use the 0.4s value for final circuits and 5s for distribution circuits only.
| Disconnection Time | Max Zs | Testing Limit (80%) |
|---|---|---|
| 0.4 seconds | 1.61Ω | 1.29Ω |
| 5 seconds | 3.2Ω | 2.56Ω |
30A Across Device Types
| Device Type | Max Zs (0.4s) | Testing Limit |
|---|---|---|
| BS 1361 Fuse | 1.61Ω | 1.29Ω |
| BS 3036 Semi-enclosed Fuse | 1.26Ω | 1.01Ω |