Skip to content

Max Zs for 30A BS 1361 Fuse

BS 7671 Table 41.4 — BS 7671:2018+A2:2022

Max Zs (0.4s)

1.09Ω

Testing Limit

0.87Ω

Max Zs (5s)

1.75Ω

Ia (0.4s)

200A

At a Glance

Device
BS 1361 Fuse30A
Standard
BS 1361
Max Zs (0.4s)
1.09Ω
Max Zs (5s)
1.75Ω
Testing Limit (80%)
0.87Ω
Ia (0.4s)
200A

About BS 1361 Fuse

BS 1361 cartridge fuses were commonly used in domestic consumer units before MCBs became standard. They are still found in older installations and are acceptable for continued use. Their max Zs values are generally more generous than equivalent MCB ratings.

Typical Circuits for 30A BS 1361 Fuse

Recommended cable sizes for 30A BS 1361 Fuse circuits
CircuitCable SizeNotes
Ring final / cooker2.5–6.0mm²Older consumer unit configuration

Worked Example: Maximum Cable Run for 30A BS 1361 Fuse

  1. Maximum Zs (tabulated) = 1.09Ω (BS 7671 Table 41.4)
  2. Testing limit (80%) = 1.09 × 0.8 = 0.87Ω
  3. Assume Ze = 0.35Ω (typical TN-C-S (PME) supply)
  4. Maximum R1+R2 = 0.87 − 0.35 = 0.52Ω
  5. Using 4mm² T&E: R1+R2 = 9.22 mΩ/m
  6. Maximum cable run = 0.52 ÷ 0.00922 = 56.4m

On a TN-C-S (PME) supply with 4mm² cable, the maximum one-way cable run is approximately 56.4m before Zs exceeds the testing limit. In practice, always measure — parallel earth paths and cable route conditions will affect the actual value.

0.4s vs 5s Disconnection Times

Fuse characteristics differ from MCBs — disconnection time depends on the time/current curve. At 30A: max Zs = 1.09Ω (0.4s) vs 1.75Ω (5s). The 5s value is higher because a lower fault current will still melt the fuse element given more time. Use the 0.4s value for final circuits and 5s for distribution circuits only.

Disconnection TimeMax ZsTesting Limit (80%)
0.4 seconds1.09Ω0.87Ω
5 seconds1.75Ω1.4Ω

30A Across Device Types

Device TypeMax Zs (0.4s)Testing Limit
BS 1361 Fuse1.09Ω0.87Ω
BS 3036 Semi-enclosed Fuse1.26Ω1.01Ω

Frequently Asked Questions

Built by Taro Schenker · Need a website for your trade business? Get in touch