Skip to content

Electrical Testing Sequence

Dead and live test order, instruments, pass/fail limits, and initial verification vs EICR

BS 7671 Chapters 64 & 65, IET Guidance Note 3

Why the Sequence Matters

The BS 7671 testing sequence is not arbitrary — each test validates the prerequisites for the next. Continuity must be proven before insulation resistance, because the IR test voltage needs a confirmed path to reach all parts of the circuit. All dead tests must pass before the installation is energised for live testing.

Dead first, live second. Regulation 641.1 requires this to minimize risk to the tester.

Initial Verification — Full Testing Sequence

#TestPhaseInstrumentPass Limit
1

Continuity of Protective Conductors

Method 1 (bridge) or Method 2 (wander lead). Null test leads first. Confirms ADS path.

DEADLow-resistance ohmmeter (4–24 V, ≥200 mA)Record R1+R2 or R2 value in Ω
2

Continuity of Ring Final Circuits

Three-step cross-connection test. Highest Step 3 reading = R1+R2 for the ring.

DEADLow-resistance ohmmeterConsistent readings across ring; r1 ≈ rn, rcpc ≈ 1.67 × r1 (2.5/1.5 T&E)
3

Insulation Resistance

Test L–N, L–E, N–E. Disconnect sensitive electronics. Use 250 V DC for IT/SPDs.

DEADInsulation resistance tester (500 V DC for ≤500 V circuits)≥ 1.0 MΩ (new installs typically >200 MΩ)
4

Polarity (dead)

Confirmed during R1+R2 test if Method 1 used. Check single-pole switches are in line conductor.

DEADLow-resistance ohmmeter / continuity testerCorrect polarity at all points
5

Earth Electrode Resistance (TT only)

61.8% rule for spike placement. Test in dry conditions for worst case.

DEADEarth electrode tester (Fall-of-Potential method)Ra × IΔn ≤ 50 V (typically Ra ≤ 200 Ω for 30 mA RCD)
6

Supply Polarity & Phase Sequence

First live test. Verify supply before energising installation.

LIVEApproved voltage indicator (GS38) / phase rotation meterL–N ≈ 230 V, L–E ≈ 230 V, N–E ≈ 0 V; correct L1-L2-L3 rotation
7

Earth Fault Loop Impedance (Ze)

Disconnect main earthing conductor from MET. Measure at origin only.

LIVELoop impedance tester (high current)TN-C-S ≤ 0.35 Ω, TN-S ≤ 0.8 Ω
8

Earth Fault Loop Impedance (Zs)

Or calculate Zs = Ze + (R1+R2). Compare against Tables 41.2–41.4.

LIVELoop impedance tester (no-trip for RCD circuits)Measured Zs ≤ 80% of BS 7671 table value
9

Prospective Fault Current (PFC)

Measured at origin. Highest of PSCC (L–N) and PEFC (L–E) is recorded.

LIVELoop impedance / PFC testerPSCC and PEFC must not exceed device breaking capacity
10

RCD Testing

Test at rated current (IΔn). Also test trip button function.

LIVERCD testerTrip at IΔn within 300 ms (non-delay); 5×IΔn within 40 ms (additional protection)
11

Functional Testing

Includes SPDs, lighting controls, interlocking devices.

LIVEVisual / manual operationAll switches, isolators, interlocks operate correctly

Initial Verification vs Periodic Inspection (EICR)

FeatureInitial VerificationPeriodic Inspection (EICR)
Regulatory basisChapter 64, BS 7671Chapter 65, BS 7671
ObjectiveVerify design and installationAssess condition for continued service
Testing sequenceMandatory, strictly sequentialFlexible, guided by professional judgment
Supply during dead testsInstallation de-energisedOften energised; begins with supply checks
DocumentationEIC (Electrical Installation Certificate)EICR (Condition Report)
Visual scopeCompliance with current BS 7671Deterioration, damage, and changes of use

Insulation Resistance Limits (Table 6.3)

Circuit VoltageTest VoltageMinimum Resistance
SELV / PELV250 V DC≥ 0.5 MΩ
Up to 500 V (standard)500 V DC≥ 1.0 MΩ
Over 500 V1000 V DC≥ 1.0 MΩ

EICR Classification Codes

C1Danger Present

Immediate risk of injury. Make safe before leaving site.

C2Potentially Dangerous

Would become dangerous if a subsequent fault occurred. Urgent remedial action required.

C3Improvement Recommended

Compliant with previous standards but not current BS 7671.

FIFurther Investigation

Issue discovered that needs more in-depth exploration beyond the standard inspection scope.

Common Testing Mistakes

MistakeConsequencePrevention
Testing before isolation is provenElectric shock risk to testerAlways use AVI + proving unit (GS38)
Not nulling test leadsLead resistance added to reading (>0.2 Ω error)Zero leads before every session
Skipping continuity before IR testIR voltage may not reach all conductorsFollow the sequence — each test validates the next
Using 500 V IR on sensitive equipmentDamage to MOVs, SPDs, electronic controlsReduce to 250 V DC or disconnect equipment
Comparing ambient Zs to table max (100%)False pass — fails at operating temperatureApply the 80% rule (or calculate temperature-corrected Zs)
Incomplete isolation during IR testParallel paths give false high readingsEnsure circuit under test is fully isolated

Safety Reminders

  • - Safe isolation before any dead testing — AVI + proving unit, lock off, prove dead
  • - Do not proceed to the next test if the current test fails — rectify the fault first
  • - Test leads must comply with GS38 — finger guards, fused, 4 mm max exposed tip
  • - Instruments must be calibrated to BS EN 61557 and within calibration date
  • - In occupied premises, communicate with occupants before isolating circuits

Key Points

  • - Dead tests first (1–5), live tests after (6–11) — minimises risk to tester
  • - Each test validates prerequisites for the next — do not skip or reorder
  • - Initial verification has a mandatory sequence; EICR sequence is flexible
  • - 80% of defects can be found during visual inspection alone
  • - Compare measured Zs against 80% of BS 7671 table values (temperature correction)
  • - Record every circuit — even untested ones (note the limitation and reason)

Built by Taro Schenker · Need a website for your trade business? Get in touch