Voltage Drop Tables

mV/A/m values for calculating voltage drop in cable runs

BS 7671:2018+A2:2022 Tables 4D1B-4J2B

Lighting Circuits

3%

Maximum voltage drop

Other Circuits

5%

Maximum voltage drop

Formula

VD = mV/A/m × Ib × L / 1000

Result in volts

Copper Conductors (Thermoplastic 70°C)

Reference: Table 4D1B

Size (mm²)
2-core / Single-phase
mV/A/m
3/4-core / Three-phase
mV/A/m
14438
1.52925
2.51815
4119.5
67.36.4
104.43.8
162.82.4
251.751.5
351.251.1
500.930.8
700.630.55
950.460.4
1200.360.31
1500.290.25
1850.2350.2
2400.180.155
3000.1450.125
Aluminium Conductors (Thermoplastic 70°C)

Reference: Table 4H1B

Size (mm²)
2-core / Single-phase
mV/A/m
3/4-core / Three-phase
mV/A/m
164.64
252.92.5
352.11.8
501.551.35
701.050.9
950.770.67
1200.60.52
1500.490.42
1850.390.34
2400.30.26
3000.2350.205
Example Calculation

Problem: 32A load on 25m of 6mm² T+E cable (single-phase)

mV/A/m value = 7.3 (from table)

VD = 7.3 × 32 × 25 / 1000

VD = 5.84V

VD% = 5.84 / 230 × 100 = 2.54%

✓ Within 5% limit for power circuit

Notes

  • • Values are for thermoplastic (PVC) insulated cables at 70°C conductor operating temperature.
  • • For thermosetting (XLPE) cables at 90°C, values will be slightly higher.
  • • Three-phase values assume balanced load. For unbalanced loads, use single-phase values.
  • • Long cable runs may require upsizing to meet voltage drop limits.
  • • Regulation 525.1 permits higher limits where the supply is from a private LV supply.